AC Cable Voltage Drop Calculator

Estimate AC voltage drop and conductor loss using entered resistance/reactance per length, power factor, phase relation and conductor-system assumptions.

Enter your values

01 / INPUT
Calculated on your device

YOUR CALCULATION

Result

—

Calculation steps

Work through one step at a time or reveal the complete calculation. The steps use your current inputs.

    How to calculate

    Apply the conventional small-drop R/X and power-factor approximation, with the correct single/three-phase multiplier and one-way length.

    ΔV=kIL(R×PF ± X√(1−PF²)); k=2 single phase or √3 balanced three phase

    Worked example

    400 V, 50 A, one-way 100 m and R=0.4 Ω/km at unity PF in balanced three phase give about 3.464102 V drop and 300 W conductor resistance loss.

    Assumptions and input details

    R and X are supplied by you for the actual operating frequency and temperature; no cable catalogue or regulatory limit is loaded. Leading current uses a negative reactive term and may produce a model voltage rise. Unbalance, neutral current, harmonics, reactance coupling, full phasor load flow, ampacity and code compliance are excluded. A result consuming all source voltage is rejected as outside the approximation.

    Unit definitions

    Unit selection is independent of language. Each selector contains only units for its physical quantity. Calculations use defined base units internally.

    Choose from 23 length definitions, including explicitly labelled regional measures. Area conversions square the length factor; geometric volumes cube it.

    Regional measures are not interchangeable merely because their names look similar. This is a documented selection, not a claim to include every historical unit.

    SI prefixes are explicit: for example, milli means one thousandth, micro one millionth and kilo one thousand. Changing a unit changes the interpretation of the entered number.

    NIST measurement tables · Japanese traditional units · Mainland China and Hong Kong unit distinctions

    Using this calculator

    Can I enter my own problem?

    Yes. Replace the example values with your own inputs. The result, calculation steps, tables and applicable diagrams update from those inputs. Blank or invalid values clear the result; example values are never silently substituted for missing inputs.

    Are the results exact?

    Results use floating-point arithmetic and displayed rounding. Read the formula, assumptions and any stated data precision before interpreting the result.

    Is my input uploaded?

    The calculation runs in your browser. No account, file upload or external AI service is required. Inputs are not saved between page reloads.

    RELATED TOOL · PHYSICSDC Wire Voltage Drop Calculator

    Estimate DC conductor voltage drop, load voltage and wire heating, or solve the conductor area for a chosen drop limit using an entered operating resistivity.

    RELATED TOOL · ELECTRICALSingle and Three Phase AC Power Calculator

    Calculate apparent, real and reactive power for a single-phase or balanced three-phase load with an explicit RMS voltage convention.

    RELATED TOOL · IDEAL AC MODELSPower Factor Correction Capacitor Calculator

    Calculate ideal fundamental-frequency reactive correction, per-capacitor capacitance and line-current change for entered lagging power factors.

    ADVERTISEMENT

    Reserved advertising space.