Room Air Exchange and Ideal Mixing Calculator

Convert entered replacement airflow to air changes per hour and model the fraction of original room air remaining under perfect mixing.

Enter your values

01 / INPUT
Calculated on your device

YOUR CALCULATION

Result

—

Calculation steps

Work through one step at a time or reveal the complete calculation. The steps use your current inputs.

    How to calculate

    Divide effective replacement flow by room volume. Under constant flow, perfect mixing and no new source of the modeled original-air tracer, its fraction decays exponentially. Reverse the decay equation for an entered remaining fraction.

    ACH=effective m³/hour/room m³; remaining fraction=exp(−ACH×hours); time=−ln(target fraction)/ACH

    Worked example

    A 50 m³ room with 100 m³/h replacement flow and an entered effective fraction of 80% gives 1.6 ACH. After 30 minutes, about 44.933% of the original-air tracer remains; reaching an entered 10% takes about 86.347 minutes.

    Assumptions and input details

    Ideal single-zone mixing model, not an air-quality measurement, health threshold or safe re-entry time. Use replacement flow that removes the modeled tracer, not ordinary recirculation without removal. Effective fraction is entered and not measured here. Constant flow, zero incoming tracer and no continuing source are assumed; dead zones, outdoor pollutants and changing conditions are excluded. One air change does not mean every original molecule is replaced. Perfect zero remaining is not reached in finite time. Zero effective flow leaves the original fraction unchanged.

    References: NIST: tracer-gas decay and building air exchange

    Unit definitions

    Unit selection is independent of language. Each selector contains only units for its physical quantity. Calculations use defined base units internally.

    The 36 volume definitions distinguish US liquid, US dry and Imperial measures. Cups carry an explicit definition. Japanese shō is 2401/1331 L and a gō is one tenth of it; the explicitly labelled 180 mL rice cup is separate.

    Regional measures are not interchangeable merely because their names look similar. This is a documented selection, not a claim to include every historical unit.

    NIST measurement tables · UK Imperial definitions · Japanese traditional units · Mainland China and Hong Kong unit distinctions

    Using this calculator

    Can I enter my own problem?

    Yes. Replace the example values with your own inputs. The result, calculation steps, tables and applicable diagrams update from those inputs. Blank or invalid values clear the result; example values are never silently substituted for missing inputs.

    Are the results exact?

    Results use floating-point arithmetic and displayed rounding. Read the formula, assumptions and any stated data precision before interpreting the result.

    Is my input uploaded?

    The calculation runs in your browser. No account, file upload or external AI service is required. Inputs are not saved between page reloads.

    RELATED TOOL · ACOUSTICSRoom Reverberation and Absorption Area Calculator

    Estimate Sabine reverberation time and the replacement surface area needed for an entered target decay time.

    RELATED TOOL · PHYSICSPipe Flow Rate and Velocity Calculator

    Convert volumetric flow and average speed in a full circular pipe. Calculate mass flow and the time to fill an entered volume.

    RELATED TOOL · MATHEMATICSExponential Growth and Decay Calculator

    Apply an entered constant growth or decay rate to an initial quantity. Compare periodic and continuous models, view a time curve and find doubling time or half-life.

    ADVERTISEMENT

    Reserved advertising space.